atmoSPheriC gaS fired burNerS
• Oxygen ............................................................................. 7 to 9% O2
• Stack Temperature .........................................................325to50F
• Draft (Water Column Inches) .......................................... -.02 to -.04wc
• Carbon Monoxide (parts per million) ............................ <100ppm
gaS fired Power burNerS
• Oxygen .............................................................................3to6%O2
• Stack Temperature .........................................................275to50F
• Stack Draft (Water Column Inches) ............................... -.02 to -.04wc
• Overfire Draft (Water Column Inches) .......................... -.02wc”
• Carbon Monoxide (parts per million) ............................ <100ppm
oil fired burNerS (#2 oil fuel)
• Oxygen ............................................................................. 4 to 7% O2
• Stack Temperature .........................................................325to60F
• Stack Draft (Water Column Inches) ...............................-.04to-.06wc
• Overfire Draft (Water Column Inches) .......................... -.02wc”
• Carbon Monoxide (parts per million) ............................ <100ppm
• Smoke ..............................................................................0(ormanufacturersrecommendation)
PoSitive overfire gaS & oil
• Oxygen ............................................................................. 3 to 9% O2
• Stack Draft (Water Column Inches) ............................... -.02 to -.04wc
• Overfire Draft (Water Column Inches) ..........................+0.4to+0.6wc
• Carbon Monoxide (parts per million) ............................ <100ppm
NOTE:Followmanufactureguidelinesforthespecificequipmentbeingserviced.
SamPle PriNt outS / rePortS
WHAT RESULTS ARE GENERALLY ACCEPTABLE
Combustion
Test
Heat Exchanger
Test
Differential
Temperature Test
Manometer Draft/
Pressure Test
Room CO
Test
6 7